AS 3740:2021 Explained: Scope, Changes from 2010, and How the NCC Calls It Up

Code and compliance

AS 3740:2021 Explained: Scope, Changes from 2010, and How the NCC Calls It Up

AS 3740:2021 is the edition NCC 2025 calls up in its wet-area provisions. What it covers, what changed from 2010 with clause references, which NCC clause calls it up for your building class, and the numbers to keep at hand.

AS 3740:2021 Waterproofing of domestic wet areas is the edition NCC 2025 calls up in its wet-area provisions (Schedule 2: Volume One F2D2; Volume Two H4D2 and H4D3; Housing Provisions 10.2.20). It replaced the 2010 edition in 2021. This guide is for the people who specify, install and certify against it. It explains what the standard covers, what changed from 2010 with clause references, which NCC clause calls it up for your building class, and the numbers you need at hand.

1. Scope

AS 3740:2021 sets minimum requirements for the materials, design and installation of waterproofing. It applies to internal wet areas in domestic buildings as defined by the NCC: bathrooms, ensuites, laundries and areas with a basin or a floor waste.

It does not cover:

  • Flooding from plumbing failure or overflowing vessels.

  • Concrete admixtures or penetrant sealers used alone.

  • Purely decorative coatings.

  • Communal wet areas such as pool changerooms.

The standard is organised in four sections plus six appendices. The sections are Section 1 Scope and general, Section 2 Design, Section 3 Materials and Section 4 Installation. The appendices are Appendix A (design considerations and risk categories), B (falls in floor finishes), C (membrane continuity testing, normative), D (a suggested installation checklist), E (compatibility) and F (moisture testing of subfloors).

2. How the NCC calls it up

Building classNCC 2025
Class 1 houses and Class 10Volume Two H4D2 and H4D3: waterproof or water resistant to Housing Provisions 10.2.1 to 10.2.6, then either AS 3740 plus 10.2.12, or the self-contained provisions in 10.2.7 to 10.2.32 (South Australia's variation of 10.2.1 names AS 3740 directly)
Class 2 to 9Volume One F2D2: waterproof or water resistant to Specification 26 and complying with AS 3740 (F2D2(1) for Class 2 and 3 buildings and Class 4 parts; F2D2(2) for bathrooms, laundries and sanitary compartments in Class 5 to 9). The rewritten Part F1 deals with external membranes, roofs and podiums, not internal wet areas

This has two consequences. First, the standard's details apply to a Class 2 apartment bathroom too. That bathroom is not "domestic" for the purposes of the standard's own scope, but F2D2 sends you to AS 3740 for installation. Second, the NCC schedule of referenced documents fixes the edition. A specification that says "AS 3740-2010" on a project assessed under NCC 2025 is citing a superseded document.

3. What changed from AS 3740:2010

The preface lists nine changes. In practice they come down to these:

ChangeWhereWhy it matters on site
Three risk categories for wet areasAppendix A.3; used throughout Section 2Category 1 (shower areas and baths with unenclosed showers) is high risk and water must be retained inside it; Category 2 is the whole bathroom outside an unenclosed shower (A.3.3); Category 3 is the bathroom outside an enclosed shower, or a wet area with no shower (A.3.4)
Shower classification: enclosed, unenclosed Type 1, unenclosed Type 2Clause 2.2Frameless screens are Type 1 unless fitted with seals and deflectors that control the spread of water (2.2.2.1(a)(i)); curtains, no screen, and screens the spray can pass are Type 2. The type drives the waterstop and extent-of-waterproofing rules
Falls stated per categoryClause 2.3Substrate under the membrane 1:100 minimum where there is a floor waste (2.3.1); shower floor finish 1:80 minimum (2.3.2); Category 2 floor finish 1:100 minimum (2.3.3); a whole bathroom designed as an unenclosed shower needs 1:80 in the substrate (2.3.5)
Unenclosed showers: 1 500 mm extentClauses 2.1.1 and 4.8.2Waterproofing extends at least 1 500 mm from the substrate connection of the shower rose (2.1.1). A Type 2 waterstop sits at least 1 500 mm from the rose (4.8.2(b)); a Type 1 waterstop sits under the splash restriction device and across the opening (4.8.2(a))
Vertical membrane terminationClause 4.6.3Shower walls: 1 800 mm above finished floor or 50 mm above the rose, whichever is higher; full height where the rose is ceiling mounted. Hobbed or stepped showers: 150 mm above the finished tile level of the floor or 25 mm above the maximum retained water level, whichever is the greater (4.6.3(a)). Hobless: 150 mm above the highest finished floor in the shower
Hobless and step-down showers detailedClauses 4.8.3 to 4.8.5, 4.15; Figures 4.8.2 and 4.8.4A step-down of at least 15 mm where the shower is within 200 mm of an exit (4.8.5(b)(iii)), or a waterstop finishing at least 5 mm above the outer floor (4.8.4); screen placement rules for each case
Linear drainsClause 4.3.2; Appendix A.6Connection details for channel drains and four whole-of-bathroom design solutions with linear drains
NichesClause 4.12.4; Figure 4.12.4Lined on all faces with a water-resistant substrate, fillets or bond breakers at every junction, base graded at least 1:100 towards the shower
Hob constructionClause 4.7Hob top falls towards the shower; no timber hobs; joints made flush before the membrane goes on
Membrane inspection and continuity testingClauses 4.5.3 and 4.5.4; Appendix C (normative)Visual inspection before any finish is laid; flood testing to C.2 only after full cure, with the shower and the outer floor tested separately where a hob or waterstop divides them
Compatibility as a systemClause 3.2; Appendix EEvery component from primer to grout must be compatible with the membrane; the "compatibility chain" in Figure E.1 is the checklist
Moisture in subfloorsClause 4.4.3; Appendix FA test method for deciding whether a concrete or timber subfloor is dry enough for the membrane
Enclosed showerUnenclosed shower, Type 2roseCategory 1screen with a waterstopunder it (4.8.3)Category 3Category 11 500 mm minfrom the roseCategory 2waterstop flush with the floor (4.8.2)wastewasteEnclosed showerroseCategory 1screen with a waterstopunder it (4.8.3)Category 3wasteUnenclosed shower, Type 2Category 11 500 mm minfrom the roseCategory 2waterstop flush with the floor (4.8.2)waste
An enclosed shower keeps Category 1 (darkest tint) inside the screen, with the waterstop under the screen and across its opening, and the rest of the room is Category 3 (lightest); an unenclosed Type 2 shower (a curtain, no screen, or a screen the spray can get past) takes Category 1 out to a flush waterstop at least 1 500 mm from the rose connection and makes the rest of the room Category 2 (mid tint). A Type 1 unenclosed shower (a frameless screen) puts its waterstop under the screen instead, but its waterproofing still runs at least 1 500 mm from the rose. From AS 3740:2021 clauses 2.1.1, 2.2, 4.8.2 and 4.8.3 and Appendix A.3.
AS 3740:2021 Figure A.6(B) diagram
Figure A.6(B) — Whole of bathroom with linear drain
AS 3740:2021 Figure A.6(A) — Whole of bathroom example diagram
Figure A.6(A) — Whole of bathroom example

4. Materials: waterproof or water-resistant

Section 3 sorts materials into two groups. Materials deemed waterproof stand alone (Clause 3.3.1). They are:

  • Stainless steel.

  • 99.9% copper to AS 1566.

  • Flexible sheet flooring with sealed and welded joints meeting AS/NZS 4858.

  • Wet-area membranes meeting AS/NZS 4858.

  • Glass to AS 1288.

  • PVC to AS/NZS 3500.2.

Everything else in a wet area is at best water-resistant (Clauses 3.3.2 and 3.3.3). Wherever the NCC requires a waterproof element, a water-resistant material needs a waterproof layer somewhere in the build-up. Our companion article on waterproof versus water-resistant materials works through the lists and the compatibility chain.

5. The numbers to keep at hand

ItemRequirementClause
Shower wall waterproofing height1 800 mm above finished floor, or 50 mm above the rose, whichever is higher4.6.3(c)
Unenclosed shower extent1 500 mm from the rose connection2.1.1, 4.8.2
Fall in shower floor finish1:80 minimum2.3.2
Fall in substrate to floor waste1:100 minimum2.3.1
Fall in Category 2 floor finish1:100 minimum2.3.3
Step-down at shower extremity15 mm minimum where the shower is within 200 mm of an exit4.8.5(b)(iii)
Membrane up wall, hobbed or stepped shower150 mm above the finished tile level or 25 mm above the maximum retained water level, whichever is the greater4.6.3(a)
Niche base fall1:100 towards the shower4.12.4
Bath walls (shower over bath)Waterproof to 150 mm above the bath edge; junctions and penetrations to 1 800 mm above the bath floor4.13.3
Hobmembrane over it and onto the floor (4.6.2)50 mm minStep-downshower floor set below the outer floor15 mm minthe 15 mm applies within 200 mm of an exit (4.8.5)Hobless, enclosedwaterstop under the screen5 mm min abovethe outer floor (4.8.4)Unenclosedwaterstop flush with the floor (4.8.2)Type 2: 1 500 mm minfrom the rose to the waterstopHobmembrane over it and onto the floor (4.6.2)50 mm minStep-downshower floor set below the outer floor15 mm minthe 15 mm applies within 200 mm of an exit (4.8.5)Hobless, enclosedwaterstop under the screen5 mm min abovethe outer floor (4.8.4)Unenclosedwaterstop flush with the floor (4.8.2)Type 2: 1 500 mm minfrom the rose to the waterstop
Four ways to stop water at the edge of a shower, drawn with the shower on the left and not to scale: a hob with the membrane taken over it and at least 50 mm onto the outer floor, a step-down, a hobless enclosed shower with a waterstop standing at least 5 mm above the outer floor under the screen, and an unenclosed shower with its waterstop flush with the floor. A shower whose edge is within 200 mm of an exit from the room must be enclosed and use one of the first three, and a step-down there must be at least 15 mm. From AS 3740:2021 clauses 4.6.2, 4.8.2, 4.8.4 and 4.8.5.

The Housing Provisions carry their own figures for a Class 1 house, and they are not identical. The floor plane must fall to the waste at between 1:80 and 1:50 (10.2.12). Shower walls must be waterproof to not less than 1 800 mm above the floor substrate (10.2.2). For a Class 1 house these apply on both routes: NCC 2025 Volume Two H4D3 requires Housing Provisions 10.2.1 to 10.2.6 in every case and adds 10.2.12 to the AS 3740 route, so the falls must sit between 1:80 and 1:50 even where the rest of the detail follows AS 3740.

6. Common errors the standard was written to stop

  • Membrane over a substrate with no fall, so water ponds under the tiles even though the tile surface drains (Clause 2.3.1).

  • A 1 800 mm wall height measured from the tile bed rather than finished floor, or ignored where a rain-head sits higher (4.6.3).

  • Type 2 unenclosed showers with the waterstop at the screen line instead of 1 500 mm from the rose (4.8.2(b)).

  • Tiling before the membrane has cured, then flood testing a wet membrane (4.5.2, C.2).

  • A primer, bond breaker or tile adhesive from a different system to the membrane, with no compatibility statement (3.2, Appendix E).

ceiling-mounted rose:membrane full height(4.6.3(d))1 800 mm minabove the finishedfloor, not the tile bed(4.6.3(c))50 mm above the roseif higher than 1 800 mmmembrane1:80 minshower floor finish falls to the waste (2.3.2)1:100 minsubstrate under the membrane (2.3.1)floor waste12345671ceiling-mounted rose:membrane full height (4.6.3(d))250 mm above the roseif higher than 1 800 mm31 800 mm minabove the finished floor, not the tile bed (4.6.3(c))4membrane51:80 minshower floor finish falls to the waste (2.3.2)61:100 minsubstrate under the membrane (2.3.1)7floor waste
Where the wall height and the falls are measured, not to scale. The membrane goes up the wall to 1 800 mm above the finished floor or 50 mm above the rose, whichever is higher, and to full height where the rose is on the ceiling; under the tiles, the substrate carrying the membrane falls at least 1:100 to the waste and the floor finish at least 1:80. From AS 3740:2021 clauses 2.3.1, 2.3.2 and 4.6.3.

7. Who may do the work

The standard is silent on who holds the trowel, but the state licensing regimes are not. Queensland and New South Wales license waterproofing as a trade in its own right. Other states regulate it through the builder's registration and the inspection regime. A waterproofing certificate from the installer, naming the system and the standard, is routine evidence at the pre-tiling inspection. It is worth specifying on every job.

Sources: AS 3740:2021 (Standards Australia), preface, Sections 2 to 4 and Appendices A, C, E and F. NCC 2025 Volume One F2D2, Specification 26, Part F1 and Schedule 2; NCC 2025 Volume Two H4D2 and H4D3; ABCB Housing Provisions Standard 2025, Part 10.2. Figures A.6(A) and A.6(B) reproduced for review and commentary. First published 1 September 2026; rewritten with clause references 2 September 2026; updated 28 September 2026 to cite NCC 2025.

Questions this guide answers

What is AS 3740:2021?

AS 3740:2021 Waterproofing of domestic wet areas sets minimum requirements for the materials, design and installation of waterproofing to internal wet areas in domestic buildings: bathrooms, ensuites, laundries and areas with a basin or a floor waste. It replaced the 2010 edition in 2021 and is the edition NCC 2025 calls up in its wet-area provisions.

Which NCC clause calls up AS 3740?

For Class 1 houses and Class 10 buildings, NCC 2025 Volume Two H4D2 and H4D3 require wet-area elements to be waterproof or water resistant to ABCB Housing Provisions 10.2.1 to 10.2.6, and then either AS 3740 plus Housing Provisions 10.2.12, or Housing Provisions 10.2.7 to 10.2.32. For Class 2 to 9 buildings, Volume One F2D2 requires compliance with AS 3740, with Specification 26 setting out which elements must be waterproof or water-resistant.

How high must waterproofing go on shower walls under AS 3740?

Clause 4.6.3(c) requires shower walls to be waterproofed to 1 800 mm above finished floor or 50 mm above the rose, whichever is higher, and full height where the rose is ceiling mounted. The Housing Provisions Clause 10.2.2 requires shower walls waterproof to not less than 1 800 mm above the floor substrate.

What falls does AS 3740:2021 require in a bathroom floor?

Clause 2.3 requires the substrate under the membrane to fall at least 1:100 where there is a floor waste, the shower floor finish at least 1:80, and the Category 2 floor finish at least 1:100. For a Class 1 house, Housing Provisions 10.2.12, which NCC 2025 Volume Two H4D3 applies on both routes, also requires the floor plane to fall to the waste at between 1:80 and 1:50.

What changed in AS 3740:2021 from the 2010 edition?

The 2021 edition introduces three risk categories for wet areas, classifies showers as enclosed or unenclosed Type 1 and Type 2, states falls per category, sets a 1 500 mm waterproofing extent for unenclosed showers, details hobless and step-down showers, linear drains and niches, and makes membrane continuity testing in Appendix C normative.

Ask it the question you were about to look up